> Capacitor
> Resistance
> Chip




|
Sensing input |
|
|
voltage |
Jumper selectable.100-130 Vac 1 phase or 190-264 Vac 1 phase |
|
frequency |
50-60 Hz nominal |
|
Power input |
|
|
Voltage |
100-264 V ac 1 phase |
|
frequency |
100-120 Hz nominal |
|
output |
|
|
voltage |
82 V d.c. @ 200 V a.c. |
|
Current |
Continuous 4 A dc. transient 7.5A for 10 secs. |
|
resistance |
15 ohms min |
|
regulation |
+/- 1.0% (see note 1) |
|
Thermal drift |
0.03% per deg. C change in AVR ambient |
|
Typical system response |
|
|
AVR response |
20 ms |
|
Filed current to 90% |
80 ms |
|
Machine volts to 97% |
300ms |
|
External voltage adjustment |
+/- 10% with 1 k ohm 1 watt trimmer |
|
Under frequency protection |
|
|
Set point |
95% Hz(see note 4) |
|
Unit power dissipation |
12 watts maximum |
|
ANALOGUE INPUT |
|
|
Maximum input |
+/- 5V dc |
|
Sensitivity |
1v for 5% Generator Volts (adjustable) |
|
Input resistance |
1k ohm |
|
QUADRATURE DROOP INPUT |
|
|
Max. sensitivity |
0.07 A for 5% droop 0PF |
|
Max. input |
0.33 A |
|
OVER EXCITATION PROTECTION |
|
|
Set point |
65 V dc |
|
Time delay |
10-15 seconds (fixed) |
|
Build up voltage |
4 volts @ AVR terminals |

> Capacitor
> Resistance
> Chip